Completeness
Inlet filters pack, oil quantity measurement unit with flowmeters (volumetric or mass); quality oil control (if required); drain pipelines system; module-shelter.
Module-shelters are fitted with load-lifting devices (hoists), electric or water heating system, lighting, ventilation, gas-content control systems, fire alarm sensors, instruments.
Automatic control system (ACS) includes:
Automated working operator place with flow process visualization program, computor panel and secondary instruments panel. ACS is placed in common control room of the unit or in the control room module, supplied by "Corporation Uraltechnostroy" LLC.
Measurement means accuracy of the Commercial Oil Registration Package conforms to the governing document RD 153-39.4-042-99. A possibility of a bottle stand connection is provided in order to implement check and control of the densimeter.
Commercial Oil Registration premise is made from modules with overall dimensions 3000x6000x2950 mm, 3000x9000x2950 mm, which may be joined together and completed in any version as per requirement of Customer and designer.
As per Customer requirement, equipment (instruments, shut-off valves, check valves) may be installed in the assemblage of Russian or import manufacture.
Our company offers additionally to the package the following:
-
Module - shelter of turbo-piston testing unit;
-
Module - shelter for "Brooks" company compact-prover;
-
Oil flow control assemblage
-
Control room assemblage
Commercial oil registration assemblage conforms to OCT 26.260.18-2004 "Technological modules for gas and oil industry. General technical requirements"
Designation
Exemplary symbolic notation when ordering Commercial oil registration assemblage (BYYH-K) in module-shelter with a range of up to 200 m3/h, operating pressure 6,3 MPa and climatic execution per GOST 15150 for moderate and cold climate: BYYH-K-200-6,3-YXL1.
Technical Data
|
Operating Medium
Operating mode |
Commercial oil
Uninterruptible |
|
Operating Pressure M Pa |
Up to 6,3 |
|
Maximum range kg/m3 |
0…300 |
|
Oil density kg/m3 |
700…950 |
|
Oil viscosity, css, max |
100 |
|
Operating Medium temperature, îC |
+5…+50 |
|
Environment temperature, îC |
+50…-50 |
|
Module inside temperature, îC, not lower |
+5 |
|
Water content in oil, %, not more |
1 |
|
Chlorous salts content in oil, mg/l, max |
2000 |
|
Solids content, %, max |
0,05 |
|
Paraffin content, %, max |
6 |
|
Power supply, V |
220/380 |
|
Power consumption, kW, not more than |
5,5 |
|
Allowable Ratio error limit of liquid net mass, % |
0,25 |
|
Allowable Ratio error limit of liquid brut mass, % |
0,35 |
|
Explosion and fire risk class according to NPB 105-03
|
A |
|
Level of fire resistance of the module per SNiP 21-01-97 |
IV |
|
Temperature inside module, C deg, min |
+5 |
|
Module Dimensions, mm:
-length
-width
-height |
9000
3000
2950 |
|