Completeness:
The pumping station is equipped with:
-
Water supply pump units 1D315-71;
-
Water circulation pump units in fire link TsNCA 38-44;
-
Pump units for foam agent solution supply ND 5000/10
-
Pump units for solution injection into foam agent vessel NMSh-25-4.0/4B1
-
Foam agent vessel V=6,3m3 (2 pcs)
-
Water collector, solution-pipelines system with stop valves
-
Leakage drain pipelines
-
Automation and instruments Complete set
Shelter-modules are completed with load-lifting devices (hoists), electrical or water heating system, lighting, heating, fire alarm and gas-content sensors.
The Fire-fighting pumping station may be located in a module-shelter and upon open frame, and is manufactured in various design execution and completeness as per Customer requirement.
An additional completeness of the pumping units with control and alarm devices as per requirement of Customer.
In case of necessity to locate two, three or more pump units in modules, these are joined in a single production premise.
The Fire-fighting pumping station premise is made of modules sized 3000x6000x2950mm, 3000x9000x2950mm, 3000x12000x2950mm, that can be joined together and completed in any option as required by customer and designer.
The Fire-fighting pumping stations conform to OCT 26.260.18-2004 "Technological modules for gas and oil industry. General technical requirements" .
Technical Data:
|
Max. output per water, m3/h |
315 |
|
Max. output per foam agent solution, m3/h |
150 |
|
Foam agent reserve, m3 |
6,3 |
|
Pump unit type for water supply:
Number, pcs
Operating
Reserve |
1D315-71
2
1
1 |
|
Pump unit type for foam agent solution supply:
Number, pcs
Operating
Reserve |
ND5000/10
3
2
1 |
|
Temperature inside module, C min |
+5 |
|
Explosion and fire risk class |
D |
|
Level of fire resistance of the module SNiP 21-01-97 |
II |
|
Ambient temperature, оC |
- 50…+50
|
|